Seed Tender Auto Shut-Off

ST3400 ยท 408000 Control Box

What's in the System

๐Ÿ“Ÿ

Seed Tracker ST3400

The scale head. Holds the preset (target) weight; its START/STOP key runs the dispense and triggers the auto cut-off. Full operation is in Digi-Star manual D3943.

๐Ÿ”ฉ

Load Cells / Weigh Bars

Under the tender frame or hopper โ€” they tell the ST3400 how much seed has been delivered.

๐Ÿ”Œ

408000 Auger Control Box

The relay box that switches the tender's own seed control. 12 V only, 10 A internal limit, with a MANUAL / AUTO toggle on top. Built for on/off style controls.

๐Ÿงต

4-Wire Pigtail

ORANGE, BLUE, RED, BLACK โ€” the only four wires you land. Colors and destinations are in the table below.

๐ŸŽš๏ธ

Spout Button / Remote

The tender's existing dispense control. The 408000 splices in-line with it so both hand and auto control still work.

๐Ÿ”‹

12 V Power

Battery / key-switch / fused 12 V to RED, ground to BLACK.

How the Auto Shut-Off Works

MANUAL passes the button/remote straight through; AUTO hands control to the scale.

1
Set the target weight on the ST3400 for the box or planter you're filling.
2
Flip the control box to AUTO and turn on the ST3400. (In MANUAL, the spout button / remote passes straight through for normal hand dispensing.)
3
Press START/STOP on the ST3400 — the 408000 drives the tender's solenoid to dispense seed.
4
At the target weight, the ST3400 tells the box to cut off — the auto shut-off.

Installation

The 408000 is 12 V only and internally limited to 10 A. It splices into the small control signal โ€” never the motor's high-current path.

1

Identify the control type

The 408000 works with two on/off seed controls: a pull solenoid (throttle-cable) or a hydraulic forward solenoid (“AUGER FWD” / “Forward Solenoid”), triggered by a spout button or remote. Variable-rate throttle or door open/close systems may need a different control box — check this before you buy or wire. If it's “other or unknown,” call us or Digi-Star first.

2

Mount the control box

Bolt or screw the 408000 by its tabs within about 2 feet of the ST3400 so the cable reaches without stretching, out of the weather and clear of moving parts.

3

Land the four wires

Follow the wire table below for your control type. Only four wires connect — ORANGE and BLUE splice into the tender's existing control circuit; RED and BLACK are power and ground.

4

Test in MANUAL

Set the switch to MANUAL and press the spout button / remote — the solenoid should activate and dispense. Then turn the auger/conveyor off.

5

Test in AUTO

Set the switch to AUTO, turn on the ST3400, and press START/STOP — the solenoid should activate. That confirms the auto path. Set a preset and run a test load; tune the preset for coast so the delivered weight lands on the number.

Four-Wire Hookup

The same four wires, landed differently for a pull-solenoid vs. a hydraulic control. ORANGE and BLUE go where the button/remote wire used to be; RED and BLACK are power and ground.

WirePull Solenoid (throttle cable)Hydraulic (forward solenoid)
ORANGEThe relay's small ‘switch’ terminal (after removing the button/remote wire from it)The (+) terminal / short wire at the forward solenoid
BLUEThe loose wire(s) you removed — from the spout button / remoteSame — the loose button / remote wire(s)
REDBattery +12 V, key switch, or fused linkBattery +12 V, key switch, or fused link
BLACKNegative / groundNegative / ground
Pull-solenoid tip: the relay that powers the solenoid has three terminals โ€” battery +12 V, solenoid +12 V, and a small ‘switch’ terminal. Leave the two big ones alone; you only move the button/remote wire off the small ‘switch’ terminal, put ORANGE there, and reconnect that wire to BLUE.

Hydraulic tip: the ‘forward’ solenoid wire is the one reading +12 V only while dispensing โ€” verify with a volt meter before you cut, since pin order varies by tender.

Troubleshooting

Most calls are the MANUAL/AUTO switch, a missing preset, or ORANGE/BLUE landed wrong.

SymptomLikely causeFix
Won't cut off at the targetBox left in MANUAL, or no preset set.Set the switch to AUTO and enter a target weight on the ST3400; MANUAL bypasses the auto cut-off.
START/STOP does nothing in AUTOST3400 off / unpowered, or RED-BLACK not landed.Confirm the ST3400 powers up with no errors; check RED to +12 V and BLACK to ground (the ST3400 has internal fuses too).
Won't dispense even in MANUALBLUE not tied to the button/remote wire, or box unpowered.Recheck the BLUE splice to the loose button/remote wire and the RED/BLACK power.
Dispenses but never stopsVariable-rate throttle or door open/close control.The 408000 is for on/off controls only โ€” a variable-throttle or door system may need a different control box. Confirm the control type.
Hydraulic: wrong function switchesORANGE landed on the wrong solenoid.With a volt meter, find the wire that reads +12 V only when dispensing (the ‘forward’ solenoid) and land ORANGE on its (+).
Trips / won't carry the loadDraw exceeds the box's 10 A limit.The 408000 is internally limited to 10 A and 12 V โ€” it switches the small control signal, not the motor's high-current path. Keep it on the ‘switch’/solenoid side.
Intermittent operationLoose butt splice or poor ground.Redo the ORANGE/BLUE splices with insulated connectors; verify BLACK is on clean frame ground.
No weight on the ST3400Load cell or cable problem.Reseat the cell connectors and check the cable; see the Cables & Pin-Outs page.
Related wiringFull harness diagrams for both control types are in Digi-Star D3967 (408000); the newer boxes are in D3977 (408221 / 408853), and ST3400 operation is in D3943. Load-cell and serial wiring is on the Cables & Pin-Outs page.

Wire colors, control types, the 10 A / 12 V limit, and the MANUAL/AUTO test procedure are from Digi-Star manual D3967 Rev A (408000 Control Box Installation for the Seed Tracker ST3400). Variable-rate throttle or door open/close systems may require a different control box โ€” confirm the control type before installing.

Setting up auto shut-off on a tender?

Tell us the tender and how it dispenses (pull solenoid, hydraulic, or something else) โ€” we'll match the control box and walk the wiring.